3.5 TROUBLESHOOTING
Problem Cause Remedy
Checkmate Devise
Gas will not flow through unit
1. Detector Tube not fully engaged
2. Clogged needle nozzle (inlet/outlet)
3. Defective detector tube
4. Rubber Septum dislodged blocking needle-nozzle
Make sure metering Cap is screwed down tight.
Blow clear with high pressure gas. Use solvent cleaner. Hone out with small diameter wire.
Try different tube
Remove obstruction
Gas flows through tube but can't reach desired Termination Pressure. 1. Low ambient temperature.
2. Partially clogged needle.
3. Defective detector tube.
4. Loose hose.
5. Insufficient gas charge.
Warm up gas or conduct two passes at 1/2 the recommended Termination Pressure.
Clean unit.
Replace detector tube.
Tighten all connections.
No Refrigerant in liquid phase.
Gas leakage 1. Broken needle.
2. Cracked detector tube.
3. Loose hose.
Replace unit
Replace detector tube
Tighten all connections
Oil Test
Refrigerant bleeds but no Oil.
1. Low system charge.
2. Fractional Hp Compressor.
3. Insufficient bleed.
Top off sight glass.
Try supplemental method (pg.5).
Be persistent and patient.
Milk system at start up (pg. 5).
Oil Flows too fast and races past Indicator 1. Bleed pressure too high.
2. Caught off guard.
Reduce volume of gas flow and insert new tube.
Be attentive to the test and always be ready to stop flow.
Vapor Test
Acid tube did not change white or yellow.
Negative for Acid. Conduct an Oil Phase test if testing a system.
Moisture tube did not change to Purple or Blue 1. Acidic Refrigerant Gas.
2. Moisture less than 1 ppm.

Conduct acid test.
Very rare condition.
Indicator layer of Moisture Tube is Purple/Blue when removed from pkg. Expired Moisture tube. Shelf life is 6 mo. to 1 yr. Longer if stored under refrigeration.