| Problem |
Cause |
Remedy |
Checkmate
Devise
Gas will not flow through unit
|
1. Detector Tube not fully engaged
2. Clogged needle nozzle (inlet/outlet)
3. Defective detector tube
4. Rubber Septum dislodged blocking needle-nozzle |
Make sure metering Cap is screwed down
tight.
Blow clear with high pressure gas. Use solvent cleaner. Hone out with small diameter wire.
Try different tube
Remove obstruction |
| Gas flows through
tube but can't reach desired Termination Pressure. |
1. Low ambient temperature.
2. Partially clogged needle.
3. Defective detector tube.
4. Loose hose.
5. Insufficient gas charge. |
Warm up gas or conduct two passes at 1/2
the recommended Termination Pressure.
Clean unit.
Replace detector tube.
Tighten all connections.
No Refrigerant in liquid phase. |
| Gas leakage |
1. Broken needle.
2. Cracked detector tube.
3. Loose hose. |
Replace unit
Replace detector tube
Tighten all connections |
Oil Test
Refrigerant bleeds but no Oil. |
1. Low system charge.
2. Fractional Hp Compressor.
3. Insufficient bleed. |
Top off sight glass.
Try supplemental method (pg.5).
Be persistent and patient.
Milk system at start up (pg. 5). |
| Oil Flows too fast and races past Indicator |
1. Bleed pressure too high.
2. Caught off guard. |
Reduce volume of gas flow and insert new
tube.
Be attentive to the test and always be ready to stop flow. |
Vapor Test
Acid tube did not change white or yellow. |
Negative for Acid. |
Conduct an Oil Phase test if testing a
system. |
| Moisture tube did not change to Purple or
Blue |
1. Acidic Refrigerant Gas.
2. Moisture less than 1 ppm. |
Conduct acid test.
Very rare condition. |
| Indicator layer of Moisture Tube is
Purple/Blue when removed from pkg. |
Expired Moisture tube. |
Shelf life is 6 mo. to 1 yr. Longer if
stored under refrigeration. |